NB-BESS Open Standard seal
Normative document

NB-BESS Open Standard v1.1

Criteria for the designation of a system as an NB-BESS — No-Break Battery Energy Storage System.

VERSION 1.1 PUBLISHED 2026-08 STATUS: ACTIVE SUPERSEDES: v1.0 MAINTAINER: NB-BESS OPEN STANDARD INITIATIVE

Disclosure — read this first

This is a young initiative, founded in 2026 by PulseVolt. Conformance under this standard is by manufacturer self-declaration supported by documented evidence. It is not a certification issued by an accredited third-party body, and the NB-BESS designation is not a certification mark.

What this standard does require is third-party certification where it already exists: criteria N-7 and N-8 are met only through listings issued by a Nationally Recognized Testing Laboratory or equivalent. This standard adds requirements on top of those listings; it never substitutes for them, nor for the safety, electrical, fire and interconnection codes of the jurisdiction of installation.

1 · Scope and purpose

This document defines the minimum criteria a stationary energy storage system must satisfy to be designated an NB-BESS (No-Break Battery Energy Storage System). Its purpose is to protect the meaning of the category: a buyer who writes "NB-BESS" into a specification must be able to rely on every criterion below being met, in the same way that "double-conversion UPS" or "Tier IV data center" carry reliable meaning.

The NB-BESS category sits at an intersection that no single existing standard covers. A system that satisfies the UPS performance and safety standards is not thereby an energy storage system; a system that satisfies the energy storage standards is not thereby free of transfer time. This standard requires both, and adds the requirements that neither family addresses: enforced protection reserve during economic dispatch, multi-source DC coupling, and instrument-grade power quality measurement at the load bus.

This document is published under an open license and may be implemented by any manufacturer at no cost. It does not reproduce the text of any referenced standard; referenced standards are cited normatively and must be obtained from their publishers.

1.1 Terms and definitions

Critical power path — the electrical path through which the protected load is served during normal operation.
Transfer time — any interval during which the protected load is not served by the system's power conversion stage.
Micro-interruption — loss or collapse of supply voltage lasting from milliseconds up to a few seconds.
Protection reserve — the portion of stored energy permanently reserved for ride-through and backup, and unavailable to economic dispatch.
Rated autonomy — the time the system sustains the protected load at 100% rated output from stored energy, from the protection reserve state of charge to the minimum permissible state of charge.
Load bus — the point of connection between the system output and the protected load, and the point of measurement for criteria N-1, N-2 and N-6.
Declaration of conformity — the manufacturer's signed statement, with supporting evidence, that a defined system family meets criteria N-1 through N-10.

1.2 Conventions

Shall denotes a mandatory requirement. Should denotes a recommendation. May denotes a permitted option. A system shall meet all of N-1 through N-10 to be designated an NB-BESS; there are no partial, tiered or graded designations.

2 · Normative references

The following documents are referenced normatively. Where undated, the latest edition applies. These documents are copyrighted and must be obtained from their publishers; this standard cites them and does not reproduce them.

ReferenceSubjectApplies to
IEC 62040-3UPS — performance and test requirements; output classification (VFI / VI / VFD)N-1, N-2
IEC 62040-1UPS — general and safety requirementsN-8
UL 1778Uninterruptible Power SystemsN-8
UL 9540Energy Storage Systems and EquipmentN-7
UL 9540ATest method for thermal runaway fire propagation in ESSN-7
UL 1973Batteries for use in stationary applicationsN-7
IEC 62933 (series)Electrical energy storage systems — terminology, parameters, safetyN-7
NFPA 855Standard for the installation of stationary energy storage systemsN-7
IEC 61000-4-30Power quality measurement methods — Class AN-2, N-6
IEC 61000-4-11 / -4-34Immunity to voltage dips, short interruptions and variationsN-2
IEEE 1159Monitoring and classification of electric power quality eventsN-6
IEEE 519Harmonic control in electric power systemsN-2
SEMI F47Voltage sag immunity for semiconductor processing equipmentN-2
ITIC (CBEMA) curveVoltage tolerance envelope for information technology equipmentN-2
UL 1741 · IEEE 1547Interconnection of distributed energy resourcesN-9
Local electrical codeNFPA 70 (NEC), NOM-001-SEDE, or the applicable code of the jurisdictionN-7

3 · Normative criteria

A system shall meet all of criteria N-1 through N-10 to be designated an NB-BESS.

N-1 Zero-transfer continuity

The protected load shall be served through the system's power conversion stage at all times during normal operation. No transfer switch, synchronization step, or direct source-to-load path shall exist in the critical power path. The output classification shall be VFI-SS-111 as defined in IEC 62040-3 — voltage and frequency independent of the input, with the highest waveform and dynamic performance classes. Transfer time at the load bus in response to any upstream disturbance shall be 0 ms, achieved by architecture rather than by switching speed.

Verification. (a) Single-line diagram review confirming that no path exists from any source to the load bus that bypasses the conversion stage during normal operation; a maintenance bypass is permitted only if it is manually initiated, externally interlocked and outside normal operation. (b) IEC 62040-3 output classification declared and evidenced. (c) Disturbance immunity testing per IEC 61000-4-11 / -4-34, or recorded field event logs from an operating installation, showing no deviation at the load bus outside the N-2 envelope. (d) Measurement resolution of at least one sample per half cycle at the load bus during the test.

N-2 Continuous power conditioning

The system shall isolate the protected load from upstream voltage sags, swells, transients, harmonic distortion, frequency deviation and micro-interruptions continuously, not only upon detection of a declared outage. Output at the load bus shall remain within the ITIC (CBEMA) tolerance envelope, and shall satisfy SEMI F47 sag immunity where the protected load includes semiconductor or equivalent precision processing equipment. Output voltage total harmonic distortion shall not exceed 5% THD at 100% linear rated load, consistent with IEEE 519 practice.

Verification. (a) Power quality measurement at the load bus using instrumentation compliant with IEC 61000-4-30 Class A, recorded during representative upstream disturbances. (b) Comparison of the recorded load-bus envelope against ITIC and, where applicable, SEMI F47. (c) THD measurement at rated load. (d) Where field evidence is used in place of laboratory testing, records shall cover a minimum of 30 consecutive days of operation and include at least one classified upstream event.

N-3 Industrial scale

The system shall be engineered, rated and serviceable for complete production lines or full facilities. Continuous rated output shall be not less than 500 kW, and the architecture shall be scalable to MW-class continuous loads. Where a manufacturer offers a product family, the 500 kW floor applies to the rated capability of the scalable family, not to the capacity of an individual delivered unit.

Verification. (a) Nameplate ratings and published product family data. (b) Thermal design and continuous-duty documentation at rated output. (c) At least one reference installation, or a type test, at or above the 500 kW floor.

N-4 Bridging and backup

The system shall (a) ride through short-duration events with zero interruption at the load bus, and (b) sustain the protected load from stored energy for its declared rated autonomy. Rated autonomy shall be not less than 5 minutes at 100% rated load, measured from the protection reserve state of charge, and the actual declared value shall be stated on the declaration of conformity. The architecture shall admit extension with on-site generation for long-duration outages without introducing a transfer event at the load bus.

Verification. (a) Autonomy discharge test at 100% rated load from the protection reserve state of charge to the minimum permissible state of charge, with the measured time recorded. (b) Where generator extension is offered, documented integration scheme plus a demonstration that generator start, synchronization and load assumption produce no disturbance at the load bus outside the N-2 envelope.

N-5 Economic operation with enforced protection reserve

The system shall be capable of energy optimization — at minimum peak shaving or tariff-driven charge management — while permanently maintaining the protection reserve. The energy management system shall enforce the protection reserve as a hard floor: no economic dispatch, optimization schedule, remote command or operator action shall be capable of discharging stored energy below the reserve required to deliver rated autonomy. The reserve value shall be declared and shall be visible to the system owner in real time.

Verification. (a) Energy management system documentation describing the reserve enforcement mechanism and the level at which it is implemented. (b) Functional test in which an economic dispatch command that would breach the reserve is issued and demonstrably refused or clamped. (c) Operating logs from an installation showing simultaneous optimization activity and reserve maintenance over not less than 30 days. This criterion is not addressed by any referenced standard and is specific to the NB-BESS category.

N-6 Measurable availability and power quality logging

The system shall continuously measure and log upstream supply conditions and load-bus performance using instrumentation compliant with IEC 61000-4-30 Class A. Events shall be classified in accordance with IEEE 1159 and recorded with synchronized timestamps. Records shall be retained for not less than 12 months, shall be exportable by the system owner in a non-proprietary format, and shall be sufficient to demonstrate, after any upstream disturbance, whether the protected load was affected.

Verification. (a) Instrument specification and evidence of IEC 61000-4-30 Class A compliance for the measurement chain. (b) Sample event report from an operating system showing an upstream event, its IEEE 1159 classification, and the corresponding load-bus record. (c) Demonstration of export and of the retention period.

N-7 Energy storage safety certification

The energy storage portion of the system shall be listed to UL 9540 (or evaluated to IEC 62933 where that framework governs), supported by UL 9540A thermal runaway fire propagation test data at the cell, module and unit levels as applicable, with battery components evaluated to UL 1973. The installation shall conform to NFPA 855 and to the electrical, fire and building codes of the jurisdiction of installation (NFPA 70 / NEC, NOM-001-SEDE, or local equivalent).

Verification. (a) Listing certificate and listing number from a Nationally Recognized Testing Laboratory or equivalent accredited body. (b) UL 9540A test reports at the applicable levels. (c) Installation-level conformity documentation for the jurisdiction, including authority-having-jurisdiction acceptance where required.

N-8 Power conversion safety certification

The power conversion stage shall be certified to UL 1778 and/or IEC 62040-1 as applicable to the market of installation, and shall carry the IEC 62040-3 output classification declared under N-1.

Verification. (a) Listing certificate or certificate of conformity from an accredited body. (b) Classification statement consistent with the evidence submitted under N-1.

N-9 Multi-source DC coupling

The system shall accept not fewer than two independent input sources — for example utility supply, on-site generation, and photovoltaic or other renewable generation — coupled such that the protected load continues to be served through the conversion stage at all times. The connection, disconnection, failure or transition of any input source shall produce no disturbance at the load bus outside the N-2 envelope, and shall not constitute a transfer event under N-1. Where the system is capable of exporting to the utility, the interconnection shall comply with UL 1741 and IEEE 1547 or the local equivalent.

Verification. (a) Single-line diagram showing source coupling topology and the point of common coupling. (b) Source transition test: with the load at not less than 50% of rated output, remove and restore each input source in turn while recording the load bus at IEC 61000-4-30 Class A resolution; no excursion outside the N-2 envelope is permitted. (c) Interconnection certification where export capability is offered. This criterion is not addressed by any referenced standard and is specific to the NB-BESS category.

N-10 Supervision, alarms and integration

The system shall provide continuous supervision with classified alarms — at minimum: informational, warning, and critical — covering conversion stage status, storage state of charge and state of health, protection reserve status, thermal condition, and upstream supply quality. Alarms shall be annunciated locally and shall be capable of remote notification. The system shall expose monitoring data through at least one open industrial protocol (for example Modbus TCP, SNMP, BACnet/IP, or IEC 61850) so that it can be integrated into the owner's existing SCADA, BMS or maintenance system without a proprietary gateway.

Verification. (a) Alarm register with classification, trigger conditions and annunciation paths. (b) Protocol point list and integration documentation. (c) Demonstration of remote notification and of a successful read by a third-party client.

3.11 Annex A — Test and Verification Methods A-1.0 · PDF

The verification paragraphs above state what must be shown. Annex A specifies how: apparatus, measurement points, procedures step by step, acceptance criteria and records to retain, for each of TM-1 through TM-10, plus the evidence index and the declaration of conformity form.

Download Annex A (PDF, 20 pp.) ↓

4 · Conformance and use of the designation

Conformance is by manufacturer self-declaration supported by documented evidence, reviewed and published by the initiative. It is not third-party certification, and the evidence trail is what gives the declaration its weight.

STEP 1

Assessment

The manufacturer assembles the evidence listed under each of N-1 … N-10 for a defined system family, including listing certificates for N-7 and N-8.

STEP 2

Declaration

The manufacturer submits a signed declaration of conformity with the evidence index and the declared values for rated autonomy, protection reserve and rated output.

STEP 3

Publication

On acceptance the system family is published in the public register, with its declared values and standard version, and the manufacturer may use the designation "NB-BESS v1.1 — declared conformance".

4.1 Use of the designation

The designation shall always be stated with its standard version and with the words "declared conformance". It shall not be presented as a certification, an approval, or a mark issued by an accredited certification body. Declared values (rated output, rated autonomy, protection reserve) shall be reproduced accurately wherever the designation is used commercially.

4.2 Transition provision

Criteria N-7 and N-8 require listings that take time to obtain. Declarations submitted before 1 January 2028 may cite listings that are formally in process, provided the testing laboratory and file number are disclosed and the register entry is marked accordingly. From that date, completed listings are required for any new or renewed declaration.

4.3 Register of declared systems

PulseVolt — founding manufacturer. NB-BESS system family, declared conformant to v1.1. MW-class systems in continuous industrial service.

The register is short because the initiative is new. Any manufacturer whose systems meet N-1 … N-10 is invited to submit a declaration at no cost — contact the initiative.

5 · Governance and versioning

The NB-BESS Open Standard initiative was founded in 2026 by PulseVolt, creator of the NB-BESS™ technology and category. The standard text is published openly and may be implemented by any manufacturer at no cost. PulseVolt administers the standard and the register during the founding phase; once three or more independent manufacturers hold accepted declarations, maintenance passes to a technical committee with one seat per declared manufacturer, and the founding administrator holds no veto.

Revisions follow semantic versioning. Substantive changes to normative criteria increment the major version and are announced with a transition period. Additions of references or clarifications increment the minor version. Current version: 1.1 (August 2026), superseding v1.0 — which contained the same architecture but lacked quantified thresholds and normative references.

NB-BESS Open Standard seal

Build to the standard

Manufacturers, integrators and specifiers are invited to use these criteria in designs, RFQs and procurement documents. A vendor-neutral specification block, ready to paste into a tender, is published at nb-bess.com/rfq.

Open the RFQ template →
NB-BESS™ is a trademark of PulseVolt. The standard text is published under an open license. Referenced standards are the property of their publishers and are cited, not reproduced.